Measurement Range |
Indoor Temperature |
32° to 110°F (0° to 43°C);
Provided by local or remote temperature sensor
|
Outdoor Temperature |
-40° to 170°F (-40° to 77°C);
Provided by remote temperature sensor
NOTE: Outdoor temperature measurement is -30° to 120°F (-34° to 49°C) if thermistor sensors are used.
|
Temperature Tolerance |
±1ºF (±0.5ºC) |
Humidity |
0% to 100% RH;
Provided by local or remote temperature sensor |
Humidity Tolerance |
± 5.0% RH |
Setpoint Range |
Auto |
38° to 99°F (3° to 37°C) |
Heat |
38° to 89°F (3° to 32°C) |
Cool |
38° to 99°F (3° to 37°C) |
Radiant Floor |
38° to 110°F (3° to 43°C) |
Humidity |
5% to 90% RH |
Power Requirements |
Power Consumption |
2.5 W @ 24VAC |
Max Current per Relay |
1A @ 24VAC |
Max Current Across All Relays |
3A @ 24VAC |
Communications |
Wi-Fi® communications |
802.11/b/g/n (2.4 GHz) |
Controls |
Up
|
Raises the room’s setpoint by 1ºF, 1ºC, or 0.5ºC, depending on the active temperature scale
|
Down
|
Lowers the room’s setpoint by 1ºF, 1ºC, or 0.5ºC, depending on the active temperature scale
|
Display |
Type |
Transflective LCD, backlit |
Size |
3.5 in. (89 mm) |
Resolution |
320 x 480 |
Connections |
C |
(1) Common from HVAC system 24VAC transformer |
RH |
(1) Reference, heat calls (W1/W2) |
R/RC |
(1) Reference, compressor/cooling calls or single reference systems (Y/Y2/G/O/B) |
W |
(1) Heat stage 1 call |
W2 |
(1) Heat stage 2 call |
Y |
(1) Compressor stage 1 call |
Y2 |
(1) Compressor stage 2 call |
O |
Non-FCU: (1) Changeover, active in cool mode;
FCU: (1) Fan call (high) |
B |
Non-FCU: (1) Changeover, active in non-cool modes;
FCU: (1) Fan call (medium) |
G |
Non-FCU: (1) Fan call;
FCU: (1) Fan call (low) |
HUM |
(1) Humidistat call |
HUMR |
(1) Reference, humidistat call |
TS1+ and TS1- |
(2) Remote sensor inputs, comprised of TS1+ and TS1- terminals;
For remote temperature sensors (CHV‑RTS, CHVI‑RTS‑1G‑N‑W, and CHVI‑RTS‑1G‑SM‑W), remote slab sensor (CHV‑RSS), remote temperature and humidity sensors (CHV‑RTHS), and 10k thermistors (all sensors and thermistors are sold separately);
Connect up to (2) Crestron temperature sensors, (1) Crestron temperature/humidity sensor, or (1) 10k thermistor;
Can be designated as an autochangeover sensor for an FCU 2-pipe heat/cool system
Note: TS1+ and TS1- connections are non-polarized. The + and - designations are provided to simplify wiring.
|
TS2+ and TS2- |
(2) Remote sensor inputs, comprised of TS2+ and TS2- terminals;
For remote temperature sensors (CHV‑RTS, CHVI‑RTS‑1G‑N‑W, and CHVI‑RTS‑1G‑SM‑W), remote slab sensor (CHV‑RSS), remote temperature and humidity sensors (CHV‑RTHS), and 10k thermistors (all sensors and thermistors are sold separately);
Connect up to (2) Crestron temperature sensors, (1) Crestron temperature/humidity sensor, or (1) 10k thermistor;
Can be designated as an autochangeover sensor for an FCU 2-pipe heat/cool system
Note: TS2+ and TS2- connections are non-polarized. The + and - designations are provided to simplify wiring.
|
USB |
(1) Micro B female, USB 2.0 computer console port for firmware upload, temporary power, and device configuration |
R CONNECTIONS Switch (on backplate) |
R/RC ONLY |
For installations with only one R connection.
Wire the R connection to the R/RC terminal. |
SEPARATE |
For installations with separate RC and RH connections.
Wire the RC connection to the R/RC terminal and the RH connection to the RH terminal. |
Sensors |
Ambient Light |
Determines Day and Night mode, and sets auto dimming range for display and LED backlight
Backlight intensity is user adjustable
|
Proximity |
Day: More sensitive
Night: Less sensitive
|
Environmental |
Temperature |
32° to 104°F (0° to 40°C)
|
Humidity |
10% to 95% RH (noncondensing) |
Construction |
Housing |
Plastic, surface-mountable to the front of a horizontally-oriented 1-gang electrical box |
Electrical Box Mounting (Preferred) |
Mountable to a horizontal US-style, 1-gang new or old work electrical box with two mounting screws (included)
|
Surface Mounting |
Mountable to dry wall with two anchors (included);
Cutout template provided
|
Mounting Depth |
1.50 in. (38 mm) |
Dimensions |
Height |
3.52 in. (89 mm)
|
Width |
4.90 in. (124 mm)
|
Depth |
1.76 in. (45 mm) overall; 0.57 in. (14 mm) from wall surface when installed
|
Weight |
7.81 oz (221 g)
|
Compliance |
Regulatory Model: M201911001
FCC Part 15 Class B, IC Class B, CE, and Intertek® Listed for US and Canada
|